Sản phẩm |
Thiết Bị Loan BáoMô tả Sản phẩm
Standard Features
Specifcations
Catalog Number 403-5A-R 403-7A-R 403-3A-R 403-8A-R UL 1971 Rated Strobe Output - candela (cd) 15 cd 15 cd 30cd 110cd UL 1638/ULC S526 Rated Strobe Output 15 cd 75 cd 30cd 110cd Strobe Flash Rate Synchronized at one fash per second. External control module necessary to meet UL 1971 synchronization requirements of 10 milliseconds over a two-hour period. Compatible Synchronization Modules G1M-RM, SIGA-CC1S, SIGA-MCC1S Strobe Operating Volts 20 to 31 Vdc (Continuous) Operating Environment INDOOR: 32-120° F (0-49° C) ambient temperature. 85% relative humidity @ 30° C Lens Markings Supplied with LKW-1 “FIRE” red letters, vertical both sides (Wall Mount) - see LKW series for optional markings Wire Connections Strobe 7 in (175 mm) color-coded polarized leads - 2 INs/2 OUTs, Bell (see 439 series cat sheet) Flash Tube Enclosure Clear LEXAN Strobe Plate, Finish CRS Steel - 5-5/16 in x 10-9/16 in (135 mm x 268 mm), red baked epoxy polyester powder-coat fnish Mounting Fits over FLUSH mounted North-American boxes - One-gang & two-gang, 3-1/2 inch & 4 inch octagon, 4 inch square Agency Listings UL 1971, UL 1638, ULC S526, CSFM, MEA, FM (All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule) |